AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 99 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
15
05-Fire Rate In boilerload_15 AV:25
data
float
25 nvoBlrLoad15 inc count (9) Output (non-polled) 30018/15
15
06-Outlet Temp
localsuptemp_1
5
AV:26
data
float
26 nvoLocSupTmp15 inc count (9) Output (non-polled) 30003/15
15
07-Display Code dispcode_15
AV:27
data
float
27 nvoDispCode15 inc count (9) Output (non-polled) 30001/15
15
08-Unit Status unitstat_15
AV:28
data
float
28 nvoUnitStat15 inc count (9) Output (non-polled) 30002/15
15
09-Run Cycles runcycles_15
AV:29
data
float
29 nvoRunCycles15 51 Output (non-polled) 30012-30013/15
15
10-Run Hours runhours_15
AV:30
data
float
30 nvoRunHours15 51 Output (non-polled) 30014-30015/15
C-More Addr 16
16
01-Fire Rate Out boilerstate_16
AV:31
data
float
31 nvoBlrState16 inc count (9) Output (non-polled) 30009/16
16
02-Active Setpoint effectsetpt_16
AV:32
data
float
32 nvoEffSetpt16 inc count (9) Output (non-polled) 30017/16
16
03-Net Remote
Setpt
setpt_16
AV:33
data
float
33 nviSetpt16 inc count (9) Input (non-polling) 40001/16
16
05-Fire Rate In boilerload_16
AV:35
data
float
35 nvoBlrLoad16 inc count (9) Output (non-polled) 30018/16
16
06-Outlet Temp localsuptemp_16
AV:36
data
float
36 nvoLocSupTmp16 inc count (9) Output (non-polled) 30003/16
16
07-Display Code dispcode_16
AV:37
data
float
37 nvoDispCode16 inc count (9) Output (non-polled) 30001/16
16
08-Unit Status unitstat_16 AV:38
data
float
38 nvoUnitStat16 inc count (9) Output (non-polled) 30002/16
16
09-Run Cycles runcycles_16 AV:39
data
float
39 nvoRunCycles16 51 Output (non-polled)
30012-
30013/16
16
10-Run Hours runhours_16 AV:40
data
float
40 nvoRunHours16 51 Output (non-polled)
30014-
30015/16
E Valve Addr 17
17
01-Cntl Output
Signal
boilerstate_17
AV:171
data
float
171 nvoEcsState17 inc count (9) Output (non-polled) 30004/17