AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 109 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip Point Name Name
Read
BACnet
N2 Type
N2
Lon SNVT
Lon
Lon Direction
ModBus
4
Air Temp SMD_BAS_IP_HTR_04_[7] AV:607 Data Float 113
inc count (9) Output (non-polled) 30607
4
Flame Strength SMD_BAS_IP_HTR_04_[8] AV:608 Data Float 114
inc count (9) Output (non-polled) 30608
4
Fire Rate In SMD_BAS_IP_HTR_04_[9] AV:609 Data Float 115
inc count (9) Output (non-polled) 30609
4
Fire Rate Out SMD_BAS_IP_HTR_04_[10] AV:610 Data Float 116
inc count (9) Output (non-polled) 30610
4
Unit Type SMD_BAS_IP_HTR_04_[11]
AV:611 Data Float 117
inc count (9) Output (non-polled) 30611
4
Unit Size SMD_BAS_IP_HTR_04_[12]
AV:612 Data Float 118
inc count (9) Output (non-polled) 30612
4
Value State SMD_BAS_IP_HTR_04_[13] AV:613 Data Float 119
inc count (9) Output (non-polled) 30613
4
Net Remote Setpt SMD_BAS_IP_HTR_04_[14] AV:614 Data Float 120
inc count (9) Output (non-polled) 30614
4
Run Cycles Upper SMD_BAS_IP_HTR_04_[15] AV:615 Data Float 121
inc count (9) Output (non-polled) 30615
4
Run Cycles Lower SMD_BAS_IP_HTR_04_[16] AV:616 Data Float 122
inc count (9) Output (non-polled) 30616
4
Run Hours Upper SMD_BAS_IP_HTR_04_[17]
AV:617 Data Float 123
inc count (9) Output (non-polled) 30617
4
Run Hours Lower SMD_BAS_IP_HTR_04_[18]
AV:618 Data Float 124
inc count (9) Output (non-polled) 30618
4
Oxygen Level SMD_BAS_IP_HTR_04_[19] AV:619 Data Float 125
inc count (9) Output (non-polled) 30619
Blr Addr 5
5
Comm Address SMD_BAS_IP_HTR_05_[0] AV:700 Data Float 126
inc count (9) Output (non-polled) 30700
5
Unit Status SMD_BAS_IP_HTR_05_[1] AV:701 Data Float 127
inc count (9) Output (non-polled) 30701
5
Fault Code SMD_BAS_IP_HTR_05_[2]
AV:702 Data Float 128
inc count (9) Output (non-polled) 30702
5
Outlet Temp SMD_BAS_IP_HTR_05_[3]
AV:703 Data Float 129
inc count (9) Output (non-polled) 30703
5
FFWD Temp SMD_BAS_IP_HTR_05_[4] AV:704 Data Float 130
inc count (9) Output (non-polled) 30704
5
Inlet Temp SMD_BAS_IP_HTR_05_[5] AV:705 Data Float 131
inc count (9) Output (non-polled) 30705
5
Exhaust Temp SMD_BAS_IP_HTR_05_[6] AV:706 Data Float 132
inc count (9) Output (non-polled) 30706
5
Air Temp SMD_BAS_IP_HTR_05_[7] AV:707 Data Float 133
inc count (9) Output (non-polled) 30707
5
Flame Strength SMD_BAS_IP_HTR_05_[8]
AV:708 Data Float 134
inc count (9) Output (non-polled) 30708
5
Fire Rate In SMD_BAS_IP_HTR_05_[9]
AV:709 Data Float 135
inc count (9) Output (non-polled) 30709
5
Fire Rate Out SMD_BAS_IP_HTR_05_[10] AV:710 Data Float 136
inc count (9) Output (non-polled) 30710
Kommentare zu diesen Handbüchern