Aerco ProtoNode Gateway Rev 3 (with external LEDs) Bedienungsanleitung Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 126
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
AERCO ProtoNode Gateway
User Manual
Page 10 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
NOTE
If there are two instances of the same MAC address, it could
result in a network crash. The node offset will allow you to avoid
this situation.
2.4.2.1 Set Node_Offset to Assign Specific Device instances for BACnet
MS/TP and BACnet/IP
If the Device Instances need to be set for addresses other than 1 to 255, change
the Node-Offset (See Figure 2-2)
The BACnet Device Instance can range from 1 to 4,194,303.
BACnet/IP and BACnet MS/TP Addressing: The BACnet device instances will
be set by taking the Node_Offset found in Web Configurator (see Figure 2-2)
and adding it to the value of the A Bank DIP switches. When more than one
device is connected to the ProtoNode, the subsequent BACnet device instances
will be sequential.
Set the PC address to be on the same subnet as the ProtoNode. See section
5.3 on how to change the IP address. (See Figure 2-2)
Open the PC browser to default IP address, which will bring you to the FST Web
Configurator for the ProtoNode.
Change the Node offset to meet the required device instance.
For example:
o Node_Offset = 20000.
o A Bank DIP Switch = 11
o Device 1 Device Instance = 20011
NOTE
The A bank dip switch setting + node offset = device instance
setting.
FIGURE 2-2: MAC Address DIP Switches