PR1: 11/30/12 Page 98 of 112
Modulex E8 Controller and BCM
Operations and Maintenance Manual
AERCO International, Inc.
100 Oritani Dr.
Blauvelt, NY 10913
Ph: 800-526- 0288
Table 9-4: BCM Standard Holding Register Address Mapping (Continued)
Data
Menu Item Units and Range
Default/(Comm
ents)
OPERATING DATA REGISTERS (Continued)
2n10
BMM #0 Capacity
(n = 0 – 7)
2n11
BMM #n Configuration
(n = 0 – 7)
0: Space Heating Only
(Read Only)
2n20
BMM #n Operating Flags (n =
0 – 7)
Bit 3: Flame detected
Bit 4: Check mode
Bit 6: Pump status
(Read Only)
1550
Firmware Code & Firmware
Revision
High byte: Firmware Code
Low byte: Firmware Revision
(Read Only)
1011 Boiler Global Capacity
12
Boiler Mode = AERCO BMS
II/ACS
13 Remote Signal = Network
3000 Burner OFF Hysteresis
9°F to 36°F (5°C to 20°C)
(Value x 10)
3002 Temp. Control: Slope Limit
2°F to 54°F/minute (1°C to
30°C/minute)
(Read/Write) 9°F
3003
Temp. Control: Proportional
Band
0°F to 90°F (0°C to 50°C)
(Read/Write) 45°F
Temp. Control: Integral Gain
3005
Temp. Control:
Derivative Gain
(Read/Write) 12