E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Page 42 of 108 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
Table 5-4: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
(Continued)
HYSTERESIS
Not Applicable
----
----
FOUND
MODULS
Displays the number of heat modules available
for service.
Display
CAP/MODULE
Displays the maximum Kw output of each heat
module.
00 1000 Kw
50 Kw:
321-1123
110 Kw: 1530-3060
NEW CONFIG
Not Applicable
----
----
MIN MOD
CASC
Not Applicable 01 08 01
HW-BOILER
Not Applicable
00 08
00
CONTR
DEVIAT
Control Deviation indicates the temperature
difference between the Boiler set point and the
actual water temperature.
Display ----
DES OUPUT
Required system output [in %]
0 100%
00
SWITCH TIME
Not Applicable
(N/A)
(N/A)
BLOCK TIME
Not Applicable
(N/A)
(N/A)
MAX T-
MODUL
Maximum temperature of Heat Module
122.0°F to
230.0°F
194.0°F
DYN
UPWARD
Not Applicable (N/A) (N/A)
DYN
DOWNWARD
Not Applicable (N/A) (N/A)
RESET TIME
Not Applicable
5 500
50
MODULAT
MAX
Start Level. If this modulation percentage is
exceeded, the next heat module is connected
after the delay time elapses.
50% - 100% 30%
MODULAT
MIN
Stop Level. If value drops below this
modulation percentage, the last heat generator
(module) of the current sequence is switched
off
10% - 60% 35%
MIN MOD HS
Not Applicable
0% - 60%
35%
MOD LEVEL
HW
Not Applicable ---- ----
SEQUENCE 1
Boiler sequence 1
12345678
SEQUENCE 2
Boiler sequence 2
87654321
EXPERT
EXPERT