Aerco KC1000 Low NOx Boiler July 2011 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Aerco KC1000 Low NOx Boiler July 2011 herunter. AERCO KC1000 Low NOx Boiler July 2011 User Manual [en] Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 115
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
REVISED JULY 7, 2011
GF-109LN
OMM-0019_0B
KC Series Gas-Fired Low NOx Boiler
USER MANUAL
Applicable to Serial Numbers G-11-0695 and above
KC Series
Gas Fired
Low NOx
Boiler System
Natural Gas and Propane Fired,
Condensing and Forced Draft Hot Water
Boiler
970,000 BTU/HR Input (Natural Gas)
1,000,000 BTU/HR Input (Propane)
Patent No. 4,852,524
Seitenansicht 0
1 2 3 4 5 6 ... 114 115

Inhaltsverzeichnis

Seite 1 - Boiler System

REVISED JULY 7, 2011 GF-109LN OMM-0019_0B KC Series Gas-Fired Low NOx Boiler USER MANUAL Applicable to Serial Numbers G-11-0695 and above KC

Seite 2 - Telephone Support

SAFETY PRECAUTIONS 1-4 (d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wa

Seite 4

APPENDIX G G-1 CONNECT 5/8'' I.D. HOSE TO CONDENSATE DRAINSHELL DRAIN VALVE *RELIEF VALVE *(NOTE 5)6''LINE SIZE BYPASSPRESSURE RE

Seite 5 - Foreword

APPENDIX G G-2 CONNECT 5/8'' I.D. HOSE TO CONDENSATE DRAINSHELL DRAIN VALVE *RELIEF VALVE * PANELS AND COVERS. LOCATE GAS PRESSURE REGULA

Seite 6

APPENDIX G G-3 CONNECT 5/8'' I.D. HOSE TO CONDENSATE DRAINSHELL DRAIN VALVERELIEF VALVESD-A-713BOILERS COMBINATION HEATING &KC LOW NOx S

Seite 8

APPENDIX H H-1 CLOSURE SWITCHPROOF OFGRNWHT60 Hz120 VAC IN20 ANEUGNDHOTNCCGNHGNDHGN123456123456789123456789101112131415123456789101112CONTROL BOX CONN

Seite 9

APPENDIX H H-2 CONTROL BOX CONNECTORSGAS FIRED BOILER SYSTEMWIRING SCHEMATIC1616131210 11 13 14 1615 17 18 19 2120 22 23 2424-PIN CONNECTOR241240 2422

Seite 10 - SAFETY PRECAUTIONS

APPENDIX I I-1 CONNECTOR BOARDP/N 124366POWER SUPPLY BOARDP/N 124362LOW WATER CUTOFF BOARD P/N 124363PMC BOARDP/N 124364IGNITION/STEPPER BOARD

Seite 11 - INSTALLATION

APPENDIX I I-2 P1P2P3P4P5P6SHELL HARNESSCONNECTOR(19 PIN)INTERLOCK HARNESSCONNECTOR(16 PIN)EXT. SENSOR/COMMHARNESS CONNECTOR(24 PIN)GAS TRAIN H

Seite 12 - LIFTING LUGS

APPENDIX J J-1 KC1000 LOW NOx DUAL-FUEL SWITCH-OVER INSTRUCTIONS The KC1000 Low NOx Boiler is shipped from the factory configured for either natu

Seite 13

INSTALLATION 2-1 SECTION 2 - INSTALLATION PROCEDURES 2.1. RECEIVING THE UNIT Each KC1000 Boiler is shipped as a single crated unit. The crated

Seite 15

APPENDIX K K-1 RECOMMENDED SPARE PARTS LISTS NOTE Refer to the Parts List Illustrations in Appendix F for the locations of the recommended and opti

Seite 17 - IN THIS BOX

03/01/05 W-1 (C102.0) STANDARD WARRANTY: Gas-Fired Hydronic Boiler Model KC-1000GWB & PWB (Propane) INTERNATIONAL, INC. PR

Seite 18

03/01/05 W-2 (C102.1) STANDARD WARRANTY: Gas-Fired Hydronic Boiler Model KC-1000GWB & PWB (Propane) INTERNATIONAL, INC. CO

Seite 20

INSTALLATION 2-2 2.3 INSTALLATION The unit must be installed with the prescribed clearances for service as shown in Figure 2.1. The minimum clearan

Seite 21

INSTALLATION 2-3 BOILERSUPPLYBOILERRETURN Figure 2.3 Supply and Return Location NOTE: The maximum working pressure for installations within the Pro

Seite 22

INSTALLATION 2-4 SHELLCAPPARTIAL TOP VIEW OF BOILERFOR INSTALLATION OF PRESS./TEMP. GAUGEPART NO. 122994-2 (PRESS. RANGE 0 – 200 PSI)PART NO. 12299

Seite 23

INSTALLATION 2-5 The location of the 1-1/4" inlet gas connection is on the right side of the unit as shown in Figure 2.7. All pipe should be

Seite 24

INSTALLATION 2-6 2.4.2 MANUAL GAS SHUTOFF VALVE A 1-1/4” manual gas shut-off valve is furnished with each unit. The valve should be positioned as sh

Seite 25 - 3.3. CONTROL PANEL MENUS

INSTALLATION 2-7 removable side panel (see Fig. 2.10). Field wiring for each particular mode of operation is described in the following paragraphs.

Seite 26 - 3.5. SETUP MENU

INSTALLATION 2-8 2.6.3 BOILER MANAGEMENT SYSTEM (BMS) MODE NOTE BMS Model 168 can utilize either pulse width modulation (PWM) or RS485 Modbus signal

Seite 27

INSTALLATION 2-9 shield is to be connected only to the terminals labeled SHEILD in the I/O Box. The sensor end of the shield must be left free and u

Seite 28

GF-109LN OMM-0019_0B KC Series Gas-Fired Low NOx Boiler USER MANUAL Telephone Support Direct to AERCO Technical Support (8am to 5 pm EST,

Seite 29 - 0 25 10

INSTALLATION 2-10 NOTE: Both the Delayed Interlock and Remote Interlock must be in the closed position to allow the unit to fire. 2.7.9.1 REMOTE INT

Seite 30 - 3.8. START SEQUENCE

INSTALLATION 2-11 from a clean area outdoors for the protection and longevity of the equipment. The more common methods of supplying combustion air

Seite 32

CONTROL PANEL OPERATING PROCEDURES 3-1 SECTION 3 - CONTROL PANEL OPERATING PROCEDURES 3.1. INTRODUCTION The information in this Section provides a

Seite 33 - SECTION 4 - INITIAL START- UP

CONTROL PANEL OPERATING PROCEDURES 3-2 Table 3-1. Operating Controls, Indicators and Displays ITEM NO. CONTROL, INDICATOR OR DISPLAY FUNCTION 1 LE

Seite 34

CONTROL PANEL OPERATING PROCEDURES 3-3 Table 3-1. Operating Controls, Indicators and Displays - Continued ITEM NO. CONTROL, INDICATOR OR DISPLAY FU

Seite 35

CONTROL PANEL OPERATING PROCEDURES 3-4 4. With the desired menu displayed, press the ▲ or ▼ arrow key. The first option in the selected menu wil

Seite 36

CONTROL PANEL OPERATING PROCEDURES 3-5 NOTE The Outdoor Temp display item shown with an asterisk in Table 3-2 will not be displayed unless the Out

Seite 37

CONTROL PANEL OPERATING PROCEDURES 3-6 3.6. CONFIGURATION MENU The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint

Seite 38

CONTROL PANEL OPERATING PROCEDURES 3-7 Table 3-4. Configuration Menu - Continued Available Choices or Limits Menu Item Display Minimum Maximum Defa

Seite 39

CONTENTS i GF-109LN - THE AERCO KC1000 GAS FIRED LOW NOx BOILER Operating & Maintenance Instructions FOREWARD A SECTION 1 – SAFETY PRECAUTIONS

Seite 40

CONTROL PANEL OPERATING PROCEDURES 3-8 3.8. START SEQUENCE When the Control Box ON/OFF switch is set to the ON position, it checks all pre-purge s

Seite 41

CONTROL PANEL OPERATING PROCEDURES 3-9 154155AIR/FUEL VALVEBLOWER PROOFSWITCHTO FRAMEHARNESS Figure 3-5. Blower Proof Switch 5. Upon completion of

Seite 42

CONTROL PANEL OPERATING PROCEDURES 3-10 Table 3-6. Relationship Between Air/Fuel Valve Position and Energy Input of a Unit Running on Natural Gas Air/

Seite 43 - MODE OF OPERATION

INITIAL START-UP 4-1 SECTION 4 - INITIAL START- UP 4.1 INITIAL START- UP REQUIREMENTS The initial start-up of the KC-1000 Low NOx Boiler is comprise

Seite 44

INITIAL START-UP 4-2 SSOV1/8" NPT PLUG(INSTALLMANOMETERHERE) Figure 4.1 1/8” Gas Plug Location 4.2.3 PREPARING THE FLUE VENT PROBE HOLE 1. I

Seite 45

INITIAL START-UP 4-3 NOTE: On initial start-up, or return to service from a fault condition, the unit will remain at a 29% valve position for two-min

Seite 46

INITIAL START-UP 4-4 15. Replace the regulator cap and cap gasket and wait for the analyzer reading to settle. 16. When the analyzer reading settl

Seite 47

INITIAL START-UP 4-5 BLOWEROUTLETBLOWERINLETSCREENSHUTTERSHUTTER LOCKING NUTS Figure 4.4 Air Shutter Locking Nut Location REMINDER: At 30% valve posi

Seite 48

INITIAL START-UP 4-6 5. Set the unit to the Manual Mode by pressing the AUTO/MAN switch. A flashing Manual Valve Position message will be display

Seite 49 - SAFETY DEVICE TESTING

INITIAL START-UP 4-7 14. Use a flat-tip screwdriver to adjust the differential pressure regulator. Turn the screwdriver: • counterclockwise to incre

Seite 50

CONTENTS ii SECTION 6 – SAFETY DEVICE TESTING PROCEDURES 6-1 Para. Subject Page 6.1 Testing of Safety Devices 6-1 6.2 Low Gas Pressure Fault Test 6-

Seite 51

INITIAL START-UP 4-8 22. Wait for the analyzer to settle and then compare the new oxygen reading to Table 6 (or 6A). Repeat the inlet air shutter

Seite 52

INITIAL START-UP 4-9 OVER-TEMPERATURESWITCHESSHELL SENSOR209TEMPERATURE SWITCH DETAILS137HARNESS136FROM SHELLNCNCCNOCLIQUID LEVEL SWITCHOVER TEMP. SWI

Seite 54

MODE OF OPERATION 5-1 SECTION 5 - MODE OF OPERATION 5.1 INTRODUCTION The following paragraphs provide detailed descriptions of the six different

Seite 55 - SECTION 7 - MAINTENANCE

MODE OF OPERATION 5-2 11. Press the CHANGE key. The display will begin to flash. 12. Use the ▲ and ▼ arrow keys to select the reset ratio de

Seite 56

MODE OF OPERATION 5-3 If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to

Seite 57

MODE OF OPERATION 5-4 If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to

Seite 58

MODE OF OPERATION 5-5 5.7 COMBINATION CONTROL SYSTEM (CCS) NOTE Only BMS Model 168 can be utilized for the Combination Mode, not the BMS II (Model 5R

Seite 60

SAFETY DEVICE TESTING 6-1 SECTION 6-SAFETY DEVICE TESTING PROCEDURES 6.1 TESTING OF SAFETY DEVICES Periodic testing of all controls and safety devi

Seite 61 - TROUBLESHOOTING

FOREWORD A Foreword This system can be operated using natural gas or propane fuel. A simple spring change in the differential regulator and com

Seite 62 - TROUBLESHOOTING

SAFETY DEVICE TESTING 6-2 HIGH GASPRESSURE SWITCH Figure 6.2 High Gas Pressure Switch 6.4 LOW WATER LEVEL FAULT TEST 1. Set the ON/OFF switch in

Seite 63

SAFETY DEVICE TESTING 6-3 6.6 INTERLOCK TESTS The unit is equipped with two interlock circuits called the Remote Interlock and Delayed Inter-lock. Te

Seite 64

SAFETY DEVICE TESTING 6-4 Figure 6.4 Manual Leak Detection Valve 6.8 AIR FLOW FAULT TEST 1. Start the unit in manual mode and set the valve positi

Seite 65

SAFETY DEVICE TESTING 6-5 SSOVACTUATORCOVERSSOVCOVERSCREW Figure 6.6 SSOV Actuator Cover Screw Location 6.10 PURGE SWITCH OPEN DURING PURGE 1. Set

Seite 66

SAFETY DEVICE TESTING 6-6 6.11 IGNITION SWITCH OPEN DURING IGNITION 1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual

Seite 67

MAINTENANCE 7-1 SECTION 7 - MAINTENANCE 7.1 MAINTENANCE SCHEDULE The unit requires regular routine maintenance to keep up efficiency and reliabilit

Seite 68

MAINTENANCE 7-2 7.3 FLAME DETECTOR The flame detector assembly (124837) is located in the body of the burner (Figure 7.1). The flame detector may be

Seite 69

MAINTENANCE 7-3 7. Loosen the 1/4” NPT union on the low NOx staged ignition assembly (Figure 7.3). 8. Disconnect the staged ignition assembly 1

Seite 70

MAINTENANCE 7-4 19. Using an 11/16” wrench, loosen the compression fittings on the feedback tube between the air/fuel valve and the differential pres

Seite 71 - RS232 COMMUNICATION

MAINTENANCE 7-5 RELIEF VALVEDRAIN VALVEREDUCING1/4" PLUGHOT WATERHOT WATERSUPPLY (OUTLET)RETURN (INLET)BUSHINGREDUCINGBUSHING Figure 7.9 Heat Ex

Seite 74

TROUBLESHOOTING 8-1 Chapter 8- TROUBLESHOOTING GUIDE 8.1 INTRODUCTION This troubleshooting guide is intended to aid service/maintenance personnel

Seite 75 - APPENDIX A

TROUBLESHOOTING 8-2 TABLE 8-1. BOILER TROUBLESHOOTING FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION AIRFLOW FAULT DURING IGNITION 1. Blowe

Seite 76

TROUBLESHOOTING 8-3 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION DELAYED INTERLOCK OPEN 1.

Seite 77

TROUBLESHOOTING 8-4 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION FLAME LOSS DURING RUN 1.

Seite 78

TROUBLESHOOTING 8-5 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION HIGH WATER TEMP SWITCH OP

Seite 79

TROUBLESHOOTING 8-6 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION IGN SWTCH CLOSED DURING P

Seite 80

TROUBLESHOOTING 8-7 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION LINE VOLTAGE OUT OF PHAS

Seite 81 - APPENDIX B

TROUBLESHOOTING 8-8 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION continued 5. Defective I

Seite 82

TROUBLESHOOTING 8-9 TABLE 8-1. BOILER TROUBLESHOOTING – Continued FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION SSOV FAULT DURING PURGE

Seite 83

SAFETY PRECAUTIONS 1-1 SECTION 1 -- SAFETY PRECAUTIONS 1.1 WARNINGS & CAUTIONS Installers and operating personnel MUST, at all times, observe al

Seite 85 - (Balco)

RS232 COMMUNICATION 9-1 Section 9 - RS232 COMMUNICATION 9.1 INTRODUCTION The RS232 port on the front panel of the C-More Control Box (Figure 3-1)

Seite 86

RS232 COMMUNICATION 9-2 (c) Menu changes will be stored in non-volatile memory. 9. To redisplay the menu and view the option which was just changed

Seite 87 - APPENDIX D

RS232 COMMUNICATION 9-3 Table 9-1. Sample Fault Log Display No. Fault Message Cycle Date Time 0 Direct Drive Signal Fau

Seite 89

APPENDIX A A-1 APPENDIX A - BOILER MENU ITEM DESCRIPTIONS MENU LEVEL & OPTION DESCRIPTION OPERATING MENU Active Setpoint This is the setpo

Seite 90

APPENDIX A A-2 APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - CONTINUED MENU LEVEL & OPTION DESCRIPTION SETUP MENU Password Allows password to

Seite 91 - APPENDIX E

APPENDIX A A-3 APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued MENU LEVEL & OPTION DESCRIPTION CONFIGURATION MENU (Cont.) Reset Ratio

Seite 92

APPENDIX A A-4 APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued MENU LEVEL & OPTION DESCRIPTION CONFIGURATION MENU (Cont.) HI DB Set

Seite 93 - APPENDIX F

APPENDIX A A-5 APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - CONTINUED MENU LEVEL & OPTION DESCRIPTION TUNING MENU Prop Band Generates a valv

Seite 94

SAFETY PRECAUTIONS 1-2 CAUTION Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean wat

Seite 96

APPENDIX B B-1 APPENDIX B - STARTUP, STATUS AND FAULT MESSAGES TABLE B-1. STARTUP AND STATUS MESSAGES MESSAGE DESCRIPTION DEMAND DELAY XX sec

Seite 97

APPENDIX B B-2 TABLE B-2. FAULT MESSAGES FAULT MESSAGE FAULT DESCRIPTION AIRFLOW FAULT DURING PURGE The Blower Proof Switch opened during purge, or

Seite 98

APPENDIX B B-3 TABLE B-2. FAULT MESSAGES - Continued FAULT MESSAGE FAULT DESCRIPTION OUTDOOR TEMP SENSOR FAULT The temperature measured by the Outd

Seite 100

APPENDIX C C-1 Temperature Sensor Resistance Chart (Balco)

Seite 102

APPENDIX D D-1 INDOOR/OUTDOOR RESET RATIO CHARTS Header Temperature for a Building Reference Temperature of 50F RESET RATIO Air Temp 0.6 0.8 1.0

Seite 103

APPENDIX D D-2 Header Temperature for a Building Reference Temperature of 65F RESET RATIO Air Temp 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 6

Seite 104

APPENDIX D D-3 Header Temperature for a Building Reference Temperature of 75F RESET RATIO Air Temp 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 7

Seite 105 - APPENDIX H

SAFETY PRECAUTIONS 1-3 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipm

Seite 106

APPENDIX D D-4 Header Temperature for a Building Reference Temperature of 90F RESET RATIO Air Temp 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4

Seite 107 - APPENDIX I

APPENDIX E E-1 BOILER DEFAULT SETTINGS MENU & OPTION FACTORY DEFAULT Setup Menu Password 0 Language English Unit of Temp Fahrenheit Comm Add

Seite 108

APPENDIX E E-2 BOILER DEFAULT SETTINGS - Continued MENU & OPTION FACTORY DEFAULT Configuration Menu --Continued Network Timeout 30 seconds

Seite 110

APPENDIX F F-2 35 (89)49 (124)57 (145)47 (119)30-1/816-3/423-1/468-1/277-1/872-1/214-3/819 (48)22-1/4 (57)15-1/2 (39)293 (8)6 (15) I.D.FLUE CONN.3/4

Seite 111 - APPENDIX K

APPENDIX F F-3 35(89)49(124)57(145)47(119)30-1/816-3/423-1/468-1/277-1/872-1/214-3/819(48)22-1/4(57)15-1/2(39)293(8)6(15)I.D.FLUE CONN.3/4(2)DIA.(ENCL

Seite 112

APPENDIX F F-4 225146DESCRIPTIONQTYITEM PART NO.BLOWER PROOF SWITCH161002-144337241138 39252623XX NOT SHOWN IN THE DRAWINGTEMP./PRESS. GAUGEDRAIN VA

Seite 113 - C102.0)

APPENDIX F F-5 6364515491752182943313230404114223727 28CPLG. W/PLUGSIGHT PORT535413PARTS LISTNORTHVALE, NJ 07647INTERNATIONAL, INC.PL-A-145(SH. 2 OF

Seite 114 - C102.1)

APPENDIX F F-6 REV.KC1000 LOW NOx BOILER IRI GAS TRAIN022305GSDWN.BY DATENTSSCALEAPPD. DATESD-A-660 CNORTHVALE, NJ 07647INTERNATIONAL, INC.AERCOSSOV

Seite 115

APPENDIX F F-7 126115917108241413DO NOT CUT WIRESITEM NO. QTY. PART NO. DESCRIPTION1 1 124866 SOLENOID VALVE, 1/4" NPT2 1 122712 1/2" NPT,

Kommentare zu diesen Handbüchern

Keine Kommentare